MPX Motor Protection Relay — Maker Industries
MPX Motor Protection Relay
Settings Tool v7.59
DISCONNECTED
Connect via Bluetooth to begin
Status
Voltage
Current
Motor
Inputs & Relays
Device
—VOLTS
Line A-B
—VOLTS
Line B-C
—VOLTS
Line C-A
—AMPS
Line 1
—AMPS
Line 2
—AMPS
Line 3
—%
AN1
—%
AN2
—%
AN3
Digital Inputs
1 — START—
2 — STOP—
3—
4—
Relay Outputs
R1—
R2—
R3—
R4—
Serial Number
—
Firmware Version
—
Total Runtime
—
Active Fault
—
Total Power
—
Over Current Lock
—
Motor Load (est.)
—
Efficiency (est.)
—
Under Voltage
Over Voltage
Phase Loss
Voltage Unbalance
Phase Rotation
Earth Fault Lockout
Enable Phase Loss to enable Earth Fault Lockout.
Pre-start interlock only — checks all three Load Input channels before allowing a start. If any reads below a fixed internal threshold, the motor is blocked from starting and the OLED shows EARTH FLT LOCKOUT. Has no effect once the motor is running. Can be assigned to a relay under any relay's Fault Response section below.
Under Current
Over Current
Short Circuit
Short Circuit X I
Instantaneous trip level, as a multiple of the Over Current threshold.
× I

De-energise Main Contactor
Current Unbalance
Start Up Time
Start Up Time
Normal current protection is suppressed for this duration after the motor starts (expected inrush). OLED shows a countdown while active.
s
Startup X I
Maximum permitted starting current on any phase during the Start Up Time window, as a multiple of the Over Current threshold. Catches a genuinely excessive starting current (e.g. locked rotor) even during inrush.
× I
Earth Leakage
Auto Start
Starts Per Hour
Pre-Start Delay
Auto Stop
Motor Efficiency
Rated Output Power
From the motor nameplate (the mechanical output, not the electrical input). Enter kW or hp (1 hp = 0.746 kW); the MPX stores kW. 0 means not set. Used only to estimate motor load and efficiency — display only, never affects protection.
Rated Efficiency
Full-load efficiency from the nameplate, 50 to 99 %. 0 means not set. Both values are needed; until then the OLED and dashboard show "--". The load and efficiency shown are estimates from the measured power and a standard loss model; efficiency is only shown above 20 % load.
%
Digital Inputs
Function
Fixed as START — not configurable
START
Contact Type
Fixed as Normally Open
NO

Function
Fixed as STOP — not configurable
STOP
Contact Type
Fixed as Normally Closed
NC

Function
Fixed as RESET — not configurable
RESET
Contact Type
Fixed as Normally Open
NO

Enable
What this input does when active
Analog Inputs

Channels 1-2 are 4-20mA current loop inputs. Each is calibrated at 6 known points via the Factory Tool (3.9mA is the Open Circuit fault threshold — not part of the working range; 4mA and 20mA are the ends of the working range; 8/12/16mA improve accuracy in between). A reading below the calibrated 3.9mA point is treated as a broken wire — the motor is stopped (or blocked from starting) and the OLED shows the channel's label followed by OPEN CIRCUIT, recovering automatically once the reading genuinely returns above 4mA. Channel 3 is different hardware — a 0-3.3V resistive input, or a digital button input, selectable below — with no calibration and no Open Circuit concept. Configure label, engineering range and unit for each. Values display on the Status tab.

Label
Minimum Value (at 4mA)
⚠ Must be lower than the Maximum Value
%
Maximum Value (at 20mA)
⚠ Must be higher than the Minimum Value
%
Unit
Assign to Relay
Optional — has that relay trigger whenever this channel crosses its own threshold, with its own direction. Only relays not already claimed by something else are selectable.
Start Trigger
Starts the motor whenever this value is in the trigger zone — evaluated continuously like a setpoint controller, not a one-time edge. Still respects Starts Per Hour, Cooling Time, and Pre-Start like any other start.
Stop Trigger
Stops (or blocks starting) whenever this value is in the trigger zone. Active only while in the zone — clears the instant it isn't, no latching.

Label
Minimum Value (at 4mA)
⚠ Must be lower than the Maximum Value
%
Maximum Value (at 20mA)
⚠ Must be higher than the Minimum Value
%
Unit
Assign to Relay
Optional — has that relay trigger whenever this channel crosses its own threshold, with its own direction. Only relays not already claimed by something else are selectable.
Start Trigger
Starts the motor whenever this value is in the trigger zone — evaluated continuously like a setpoint controller, not a one-time edge. Still respects Starts Per Hour, Cooling Time, and Pre-Start like any other start.
Stop Trigger
Stops (or blocks starting) whenever this value is in the trigger zone. Active only while in the zone — clears the instant it isn't, no latching.

Label
Input Mode
Digital lets this channel work as an extra Start/Stop button input instead of an analog sensor — for when more digital inputs are needed than IP4 alone provides.
Value @ Highest Ω
%
Value @ Lowest Ω
Confirm values against your sensor's datasheet.
%
Unit
Assign to Relay
Optional — has that relay trigger whenever this channel crosses its own threshold, with its own direction. Only relays not already claimed by something else are selectable.
Start Trigger
Starts the motor whenever this value is in the trigger zone — evaluated continuously like a setpoint controller, not a one-time edge. Still respects Starts Per Hour, Cooling Time, and Pre-Start like any other start.
Stop Trigger
Stops (or blocks starting) whenever this value is in the trigger zone. Active only while in the zone — clears the instant it isn't, no latching.
▾ Display
Additional Info Screen
Adds an additional OLED page, shown for 5 seconds at a time between the normal view, with the four relay states on the top line, total kW below it, and the estimated motor load and efficiency below that. Load and efficiency need the Motor Efficiency values on the Motor tab. The status line always stays visible.
Sending Settings
0%
Password Required
Safety Setting
This is a safety setting. Disabling it requires the admin password.