Channels 1-2 are 4-20mA current loop inputs. Each is calibrated at 6 known points via the Factory Tool (3.9mA is the Open Circuit fault threshold — not part of the working range; 4mA and 20mA are the ends of the working range; 8/12/16mA improve accuracy in between). A reading below the calibrated 3.9mA point is treated as a broken wire — the motor is stopped (or blocked from starting) and the OLED shows the channel's label followed by OPEN CIRCUIT, recovering automatically once the reading genuinely returns above 4mA. Channel 3 is different hardware — a 0-3.3V resistive input, or a digital button input, selectable below — with no calibration and no Open Circuit concept. Configure label, engineering range and unit for each. Values display on the Status tab.
| Register (address) | Value | Scaling |
| 40001 (0) | VAB — Line A-B Voltage | whole volts |
| 40002 (1) | VBC — Line B-C Voltage | whole volts |
| 40003 (2) | VCA — Line C-A Voltage | whole volts |
| 40004 (3) | IA | amps ×10 |
| 40005 (4) | IB | amps ×10 |
| 40006 (5) | IC | amps ×10 |
| 40007 (6) | Earth Leakage | mA ×10 |
| 40008 (7) | Status | 0=READY 1=RUNNING 2=FAULT 5=SETTINGS * |
| 40009 (8) | Fault reason | code — see list below |
| 40010 (9) | Total active power | kW ×10, SIGNED int16 † |
| 40011 (10) | Motor load (estimate) | % ×10, 65535 = not available ‡ |
| 40012 (11) | Motor efficiency (estimate) | % ×10, 65535 = not available ‡ |
| # | EVENT | DETAILS |
|---|---|---|
| Press REFRESH to load log from device | ||
Receive firmware update over Bluetooth.
Connected to MPX. Clicking below will switch the device into update mode. Once it restarts, use the main CONNECT button above to reconnect, then return here — the upload step will unlock automatically once you're connected in update mode.
No MPX firmware connection. If the device is already in update mode (advertising as MPX, without its serial number in the name), connect using the main CONNECT button above, then return here to upload firmware.
Device is restarting into update mode. Once it has restarted, click the CONNECT VIA BLE button at the top of the page and select MPX again, then return to this tab to upload firmware.
Firmware updated successfully. The MPX is restarting with the new firmware. Connect normally when ready.